Wire installation: direction a factor

Wire installation: direction a factor

Don Ganiere

Ottawa, Illinois

“Back-Wiring Poses Fire Hazard” correctly pointed out the hazard that may result from the use of push-in type wiring devices. In my 22 years as an electrician, I have come across many similar-type problems that did not cause fires. Unfortunately, the term “back-wired” is used incorrectly to refer to push-in devices.

The term “back-wired” as used by manufacturers of wiring devices and the electrical trade does not include push-in type devices. A back-wired device is one in which the wire is stripped, inserted into a hole in the back of the device, and then tightened with a screw to secure it and complete the connection. The connection made on a back-wired device is in every way equivalent to that made by the traditional method of wrapping the wire around the screw and tightening the screw. Using back-wired devices saves a small amount of labor at each termination, which can add up on a large project. I have never run across a problem caused by a back-wired device. Back-wired devices typically are of higher quality than push-in devices.

Push-in type devices are used because they are usually cheaper than back-wired devices and provide even more labor savings. However, they can become a hazard because of the small contact area and poor contact pressure. A jurisdiction would be wise to prohibit the use of push-in wiring devices, but please don`t paint back-wired devices with the same broad brush.

Hand entrapped in rope gripper

Elevator Rescue: Rope Gripper Entrapment

Mike Dragonetti discusses operating safely while around a Rope Gripper and two methods of mitigating an entrapment situation.
Delta explosion

Two Workers Killed, Another Injured in Explosion at Atlanta Delta Air Lines Facility

Two workers were killed and another seriously injured in an explosion Tuesday at a Delta Air Lines maintenance facility near the Atlanta airport.