Construction Concerns: Char as Fire Protection

By Gregory Havel

For more than a century, it has been proposed that a layer of char on the surface of heavy timbers acts as insulation and will slow or prevent further burning of the wood. This proposal was questioned by Francis Brannigan in 1971 and 1982 in the earliest editions of his (and its other authors) book Building Construction for the Fire Service. Yet buildings of wood construction, whether of heavy timber, wood frame, or lightweight wood structural components continue to burn and are destroyed by fire. If there were merits to this proposal, spectacular photos and videos of these fires would not appear as often as they do on televised news broadcasts or on the Internet.

This proposal is again being used by the people who today promote the use of “mass timber” in construction, which includes glulams, “cross laminated timber [CLT],” “nail laminated timber,” and other variations.  

The U.S edition of the Cross Laminated Timber Handbook is free to download at https://www.thinkwood.com/products-and-systems/clt-handbook. It is distributed by the American Wood Council, the Wood Products Council, and other organizations and government agencies. It restates this proposal in Chapter 8, “Fire Performance of Cross Laminated Timber Assemblies.” However, it states in the later sections of Chapter 8 that in the full-scale fire compartment tests in a test building of CLT construction, the walls, and ceilings of the test rooms were protected with gypsum drywall board.

Char may be an insulating material, but only when it has been cooled to the ambient temperature and isolated from the fire which created it from wood. Since char is mostly carbon (fuel) and ash, it can be easily ignited. If it were not, charcoal would not be such a popular fuel for outdoor cooking.

I propose that char on the surface of wood that is still burning is not an insulator; rather, it is still fuel at or above its ignition temperature and is part of the combustion process. As the wood timbers; load-bearing laminated columns, beams, and laminated walls and floor panels; and other structural members continue to char, more of the cross section of the load-bearing wood will be replaced by char, which has little strength, either compressive or tensile. Eventually, enough wood will be converted to charcoal and combustion gases (water vapor, carbon dioxide, and others) that the safety factor of the structural members will be burned away, leaving that part of the building subject to structural collapse (photo 1).

(1) Photo by author.

 

If a layer of char had the insulating value that is proposed by the advocates of renewable, sustainable, and “green” construction materials and methods, campfires and fireplace fuel sets using logs would self-extinguish after a short time because of the proposed insulating value of the char formed by combustion. Yet, anyone who has ever enjoyed these fires will recognize that these pieces of wood, with large cross-sectional dimensions, will burn until they are completely consumed or unless someone intervenes by applying water or another extinguishing agent to the fuel.

The officials and organizations that develop and revise building and fire codes have accepted, as fact, the proposal that a layer of char on heavy timber acts as an insulator, despite the history of serious fires in buildings of heavy timber construction. To preserve the lives of the future generations of occupants of these new mass timber buildings as well as the lives of future generations of firefighters who will respond to fire alarms in these buildings, today’s fire service must insist that any building of heavy timber or mass timber construction must provide the following:

  • A fire-resistive material like gypsum drywall board over the surfaces of any heavy timber or mass timber components exposed in any room or means of egress from any building that uses these structural components and construction methods. This requirement would permit a room contents fire to burn longer without involving combustible structural members.
  • A working automatic fire sprinkler system meeting the requirements of National Fire Protection Association (NFPA) 13, Standard for the Installation of Sprinkler Systems, rather than NFPA 13R, Standard for the Installation of Sprinkler Systems in Low-Rise Residential Occupancies. This requirement would allow fire sprinklers to discharge water on a room-and-contents fire to control it until the arrival of firefighters or even to extinguish it before the fire had grown enough to char and involve large-dimension structural members.
  • As in many life-safety systems, redundancy is the key. The presence of gypsum drywall board to protect the structural members from ignition, combined with the presence of an automatic fire sprinkler system to control or extinguish the fire, is a better assurance that the fire will be confined to its room of origin on arrival of firefighters than either alone. There is similar redundancy in the requirement for a backup power supply (batteries or a generator) for fire alarm and smoke detector systems, for fire department connections on automatic fire sprinkler and standpipe systems to supplement the city water supply, for multiple means of egress from every level of a building rather than a single stairway, for portable fire extinguishers in commercial kitchens that are compatible with the extinguishing agent used in the extinguisher systems in the hoods and ducts over the kitchen appliances, and for multiple safety controls and pressure relief valves on heating and power boilers.

These requirements are needed, whether the mass timber building is of low-rise or high-rise construction, as is proposed for New York City, Milwaukee, and Chicago.

Download this article as a PDF HERE (279 KB)

 

Gregory HavelGregory Havel i a member of the Town of Burlington (WI) Fire Department; a retired deputy chief and training officer; and a 40-year veteran of the fire service. He is a Wisconsin-certified fire instructor II, fire officer II, and fire inspector; an adjunct instructor in fire service programs at Gateway Technical College; and safety director for Scherrer Construction Co., Inc. Havel has a bachelor’s degree from St. Norbert College, has more than 40 years of experience in facilities management and building construction, has a Chief Power Plant Operating Engineer license from the American Society of Power Engineers (ASOPE), and presents classes at FDIC and other venues.

 

MORE CONSTRUCTION CONCERNS

Boiler Controls and Safety Devices

Heating Appliance and System Maintenance

Foundations, Part 2

Foundations, Part 1

Concrete Reinforcement

Greenhouses

Responsibility

Hand entrapped in rope gripper

Elevator Rescue: Rope Gripper Entrapment

Mike Dragonetti discusses operating safely while around a Rope Gripper and two methods of mitigating an entrapment situation.
Delta explosion

Two Workers Killed, Another Injured in Explosion at Atlanta Delta Air Lines Facility

Two workers were killed and another seriously injured in an explosion Tuesday at a Delta Air Lines maintenance facility near the Atlanta airport.