Construction Concerns: Lightning Protection

By Gregory Havel

For centuries, lightning strikes have caused serious damage and fires to buildings and other structures, and have also killed the occupants of buildings that were struck. Protection of structures from the effects of lightning strikes is more precise today than it was in 1752 at the time of the experiments and the original invention of lightning protection by Benjamin Franklin.

The original lightning protection system of that era included a number of metal rods attached to the walls and roof of a building. These rods were connected by copper wire, which was connected to metal rods driven 10 feet into the ground. When lightning struck, it usually struck a rod and its energy was transferred to the ground by the lightning rods, cables, and ground rods. The alternative to this is that energy being transferred to high-impedance or non-conductive building materials.

Lightning and its effects on buildings have been studied for more than 250 years. Today’s lightning-protection system as defined in National Fire Protection Association (NFPA) Standard 780, Standard for Installation of Lightning Protection Systems, 2011 edition:

NFPA 780:3.3.22* Lightning Protection System. “A complete system of strike termination devices, conductors (which could include conductive structural members), grounding electrodes, interconnecting conductors, surge protective devices, and other connectors and fittings required to complete the system.”

The basic principle in protecting life and property from lightning is to provide a path by which the electrical energy can enter or leave the earth without damaging the structure. The low-impedance path provided by metal rods, cables, and grounding electrodes is ideal for this purpose, provided that the path is continuous from the grounding electrode to the terminal on the building.

The parts of a building most likely to be struck by lightning are the edges, corners, ridges, and dormers; The other parts most likely to be struck are those that project above the surrounding parts of the building, like chimneys, spires, railings, skylights, and dormers.

A lightning strike begins with the differences in electrical charges of a cloud and the ground. Usually the cloud has a negative charge and the ground a positive charge, although occasionally this is reversed. The negative charge in the cloud forms a leader discharge channel and a low-current discharge that progresses toward the earth. When the lower end of the downward leader approaches the ground or a grounded object, upward leaders are initiated from prominent points and extend toward the downward leader. The high-current return stroke begins when the upward leader connects with the downward leader.

The primary principle in lightning protection is to ensure that there is a high probability that the leader that connects with the downward leader originates from an air terminal, and not from a part of the structure that will be damaged by the electrical energy that will flow through it. For a detailed explanation of the mechanics of a lightning strike and the functioning of a lightning protection system, see NFPA 780–2011, Annex B.

Construction Concerns for Firefighters: Lightning Protection

(1)

Elevated air terminals (photo 1) provide the protection required, provided that they are located systematically and as required by NFPA 780. These air terminals provide protection for the area spread out below them, called a “zone of protection.”

These air terminals are designed to be mounted to different types of surfaces (photos 1 and 2) and to different types of materials using connectors that will not be corrosive either to the material of the air terminal or to the material to which it is attached.

Note that most air terminals are short and taper to a point. In the dark, smoke, rain, or fog, these can pose a trip and impalement hazard to firefighters on the roof.

Air terminals are also used to protect projections above the roof and metallic objects on the roof, like the metal chimney in photo 1. The air terminals are connected to a main conductor cable (photos 1 and 2), which is connected to two or more down conductors (photo 3) each with its own grounding electrode or rod.

Photo 1 shows a section of a roof with three visible air terminals: one on the shingled ridge at the left center of the photo; one on the shingled gable at the right center; and the third on the metal chimney to the right of the gable. The main cable connecting these is also visible running from the ridge to the gable and onto the roof of the attached metal greenhouse.

Construction Concerns for Firefighters: Lightning Protection

(2)

Photo 2 shows the air terminal at the gable of the greenhouse with the main cable running along the ridge from the left and down the right slope of the gable at the right, toward a down conductor.

Construction Concerns for Firefighters: Lightning Protection

(3)

Photo 3 shows a down conductor attached to a brick wall and connected to the cable leading to the grounding electrode.

A second component of a lightning-protection system is common ground bonding. Chapter 4.14 of NFPA 780 calls for interconnection, or bonding, of all grounding conductors and buried metallic conductors that could provide a path for lightning currents, to provide a common ground potential. This interconnection includes lightning protection, electric service, communications, antenna systems, and underground metallic piping (water service, well casings, conduits, and gas piping on the customer’s side of the meter). See the May 2009 “Construction Concerns” article regarding bonding requirements for corrugated stainless steel tubing (CSST).

The third component of a lightning-protection system is permanently-installed surge protection for the building’s electrical system, communications systems (cable TV, alarm systems, antenna systems, and data cables). Surge protection must be installed at all electric service entrances; at the entrances of communications systems; and at the point where any of these leave the building to supply another structure with a cable run of more than 100 feet (30 m). Supplemental surge protection may also be installed at branch circuit panels and at the point of use.

Permanently installed surge protection devices protecting electric services, as well as communications systems, must be installed and grounded according to the requirements of NFPA 70 National Electrical Code. Surge protection devices must be grounded through the electrical system grounding conductor, rather than directly to the down conductor of the lightning protection system.

Lightning-protection systems installed before 2000 may be found without surge protection since these devices are relatively new technology. Instead, they may have a lightning arrester installed on the electrical service disconnect switch. Systems installed before 1980 may have neither surge protection nor lightning arrester.

Even though lightning-protection systems for buildings are low in cost when compared to the price of a building, many building owners and code officials are not convinced that these are necessary. After many lightning storms, there are reports to emergency services of fires, smells of smoke, and building damage. In addition, many buildings in the area will replace electrical and electronic devices (computers, televisions, telephone systems, electrical appliances, alarm system components, and even lighting fixtures) even if those buildings were not struck directly by lightning. It is a common perception that property insurance will cover the damage–but it will not cover the inconvenience during the evaluation and replacement, or the frustration of the building’s occupants if they are displaced for a week or a month while the building is repaired.

When firefighters respond to storm-related incidents involving lightning, we should note on our reports whether any lightning protection systems were installed and if they functioned properly or were damaged. Accumulation of this kind of data can lead to changes in the building and fire codes that would require these systems in all new or renovated structures.

Download this article as a PDF HERE.

Building construction for firefighters: Greg HavelGregory Havel is a member of the Town of Burlington (WI) Fire Department; retired deputy chief and training officer; and a 30-year veteran of the fire service. He is a Wisconsin-certified fire instructor II, fire officer II, and fire inspector; an adjunct instructor in fire service programs at Gateway Technical College; and safety director for Scherrer Construction Co., Inc. Havel has a bachelor’s degree from St. Norbert College; has more than 30 years of experience in facilities management and building construction; and has presented classes at FDIC.

 


MORE CONSTRUCTION CONCERNS

Hand entrapped in rope gripper

Elevator Rescue: Rope Gripper Entrapment

Mike Dragonetti discusses operating safely while around a Rope Gripper and two methods of mitigating an entrapment situation.
Delta explosion

Two Workers Killed, Another Injured in Explosion at Atlanta Delta Air Lines Facility

Two workers were killed and another seriously injured in an explosion Tuesday at a Delta Air Lines maintenance facility near the Atlanta airport.